CLEANROOM PACKAGE SOLUTIONS

显示标签为“clean room”的博文。显示所有博文
显示标签为“clean room”的博文。显示所有博文

2015年3月11日星期三

The difference between the clean room and clean booth(Modular clean room)

More and more customer prefer easy installed clean booth(Modular clean roo, softwall clean room as named) for cost saving, to keep a clean area space.
Then Anlaitech company engineer would take more information about clean booth to share, if any professional in clean room trade, we would much appreciated your comments !
Thank you for reading.

The difference between the clean room and clean booth(Modular clean room)


 

1. Clean booth material :

Framework of clean booth generally three types:50*50/50*80/50*100 stainless steel square but, iron with epoxy powder coated in square tube , 40*40 aluminum.
The top shelf material of clean booth generally four types: stainless steel plate, cold rolled steel spray epoxy, anti -static air curtain, (anti-static ) acrylic plate .
Airflow Supply Parts, the general choice FFU laminar flow hood (FFU laminar flow air supply unit )
Walls of clean booth materials generally include: anti-static air curtain, ( anti-static ) acrylic plate.


2.Clean booth purification level of choice:

More customers will choose 1000class clean booth(Modular clean room), or 10000class clean booth, a small number of customers will choose one hundred or ten thousand clean class clean booth. In short , clean booth-level choices depends on customers requirements, but relatively clean booth sealed closed, such as when selecting clean booth level is relatively low, often bring some side effects : insufficient cooling capacity, staff feel more hot in the clean booth, so the actual and the customer communication process , need to pay attention to this point.

3. The cost of the clean room and clean booth comparison:

Overall, most customers will built clean booth in the clean room, but some customers do not want to build a clean room, clean booth does not consider air conditioning system and air shower room, pass box these cleaning equipment, etc. the cost of clean booth is about 40% to 60% of the clean room cost, also depending on the customer 's choice of clean booth material, as well as the size of the clean booth. The larger the area needs, with a clean room cost difference will be smaller compared.

4. clean booth advantages:

A. Construction fast, easy installation
B. low cost , easy maintenance
C. easy to control , FFU each comes with fan;


5. clean booth drawbacks:

A. because of the extensive use of FFU air filtration units , so clean booth noise may be relatively large ;
B. FFU own fans, to maintain high frequency, but most clean room choose FFU own fans instead of HEPA filter box also maintain high frequency;
C. due to space airflow supply , clean shed inside will often feel hot ;
D. If not clean booth built in the clean room, due to the lack of protection in effect filter, high efficiency filter life compared with the clean room, will be shortened, the higher the cost of long-term use.

We are in clean room business many years, chose Anlaitech to built a perfect clean room for your factory!
www.cleanroomffu.com
Email at: wangvanlu@gmail.com / sales@anlaitech.com
We are in Guangzhou China.


2014年7月15日星期二

Clean room Clean Class Level Definition

Clean room clean class level definition: clean room clean class level of their main point unidirectional flow, non- unidirectional flow two ways.


Unidirectional flow (1-100 class):
1- 100 class clean room, organizations are using the one-way flow of air supply, clean indoor air that same section at any point, airflow direction and speed are consistent, This allows clean room air like “piston ", as indoor dust particles fastest away. To achieve the “piston " effect, HEPA filter needs full covered of room ceiling can be achieved only charge a one-way direction of airflow.

Non- unidirectional airflow (1000-100.000 class) clean room:
1000- 100.000 class airflow direction is different with above 100class clean room, indoor air is uneven parallel flow velocity was not accompanied by reflow or vortex , which mainly depends on the continuous flow of clean indoor air dilution , will gradually discharge DC high voltage generator indoor pollution , to achieve purification . achieve different purification level, mainly by the amount of air per unit time to the performance of the different.





2014年6月26日星期四

Optical Products Clean room--LED Industrial Cleanroom Project

Optical Products clean room generally applicable to electronic instrumentation, computer, semiconductor plants, automotive, aerospace industry, lithography, micro machine manufacturing and other industries , in addition to air clean class level, but also to guarantee the achievement in addition to static requirements. The following represent the most modern LED industry as an example, photoelectric optical industry clean purification plant
LED purification plant engineering installation and construction Case Study: In this design, there is the end of some of the purification process of installing clean room, its purification cleanliness is generally one thousand or ten thousand or a hundred thousand grade purification clean room installation.

Backlit screen class cleanroom installation of these products are mainly press shop, assembly purification clean room, its cleanliness is generally ten thousand or one hundred thousand purification clean room.

LED indoor air clean room installation parameters required :
    1 ) Temperature and humidity requirements: temperature is generally 24 +2
, relative humidity of 55 +5%.
    2)  Large fresh air. As these purification clean room most are personnel, you can take the following should be the maximum value according to the following values: non- unidirectional flow clean room workshop purify total air volume 10-30 %; compensation indoor ventilation and keep the interior positive the amount of fresh air required pressure value; ensure indoor fresh air per person per hour of ≥ 40m3 / h.

   3)  Air volume supply. In order to meet the clean class level, the heat and humidity balance within the clean purification plant, require a larger air volume, on 300 square meters of workshops , ceiling height of 2.5 meters , if it is thousand grade purification clean room, air volume on need 300 × 2.5 × 30 = 22500m3 / h of air volume ( ACH is ≥ 25 times / h); If you are one hundred thousand purification clean room, air volume you need 300 × 2.5 × 20 = 15000m3 / h of air volume ( ventilation frequency is ≥ 15 times / h).

LED PRODUCING PLANT


 LED TESTING ROOM

LED SELANT PACKING ROOM: 10000CLASS

2014年6月2日星期一

GMP Clean room renovation equipment and instruments -100L dust particle counter

GMP Clean room renovation equipment and instruments -100L dust particle counter

1. The main feature:
● sample volume 100L / min of
● Built-in flow sensor
● Touch screen control operation
 ● M3/100L unit selection
 ● Count report meets GMP/ISO14644/209E, ISO21501-4


2. Specification
Dimensions
280 x 380 x 340mm3(宽××高)
Display
800,480 16.7M resolution color touch screen touch / display
Weight
6kg
Maximum power consumption
80W
Power supply
AC220V 50Hz
Size channels
0.51351025μm
Test mode
Single , repeated continuously calculates , GBMODEL (UCL)
Sampling flow
Imported sampling pump 100L/min
Sampling time
Optionally between 1 second and 99 minutes 59 seconds
Sampling frequency
1-99 times or continuous testing
Self-Purification time
≤10min
Printer
Built-in thermal printer
Counting alarm
Any value set for each channel
Maximum allowable concentration sampling
35000 / L
Extended working hours
8Hourse
Light and life
Semiconductor lasers ( life of more than 30,000 hours )
Data Storage
2000 group
Environmental Conditions
Temperature10-35
Humidity20%-75%
Optional
Stainless steel measuring aids ( optional built-in rechargeable battery pack )