2014年5月27日星期二
Clean Room Equipment: Air Shower,Pass Box,HEPA filter,Fan filter Unit HS Code
AIR SHOWER 8414809090
Dynamic pass box 841480
CLEAN BENCH 8414809090
FAN FILTER UNIT 8414809090 / 8414609090
PASS BOX 732690
HEPA unit 732690
HEPA UNIT 8421999000
Air Shower components 8414909090
HAND CLEANER
CLEAN BOOTH 8414809090
PRE-FILTER 8421999000
MEDIUM FILTER 8421999000
HEPA FILTER 8421999000
ULPA FILTER 8421999000
CLEAN ROOM
Cleanroom Materials
EPS ceiling panel 彩钢板 7326909000
Aluminum U channel U型槽 ;vh
Al-Alloy circular arc 圆弧 7604210000
Aluminum round molding 圆柱 7604210000
Aluminum U channel U型槽 7604210000
Aluminum T runner T型条 7604210000
Al-Alloy External corner column 角柱 7604210000
Al-Alloy External arc角弧 7604210000
Clean room window 窗料
Door frame 门料 门把手(金属制)8302410000
拉钉 7318140001 非用于民用航空器维护和修理的自攻螺钉
Silicon sealant 玻璃胶
Door lockset 闭门器
Door closer 门锁
Hinges 合页
sandwich panel slide door平移门
sandwich panel access hole检修门
Al-Alloy transparent window玻璃窗
AL-Alloy Shutter百叶
Steel angle角铁
Gasket 法兰棉
AL-Alloy Shutter 百叶
Electronic Formula 灯
Electronic Formula with emergency device 灯的镇流器
suspension bracket丝杆
turnbuckle 花兰
风淋室配件:
FAN 离心风机 8414593000
Pressure gage 压差表 9026209090
Positive pressure damper 余压阀
Proximity sensor 接近传感器
Photoelectricity switch 光电开关/红外感应
Control unit急停开关
Pushbutton and indicators 指示灯
AC Contactor 交流接触器
Pusheng box 保险座
Magnet for front and back door 前/后门磁
Bolt gun 喷射枪
Bolt gun mouth 喷嘴 8409919940
Fluorescent tube 荧光灯管
Fluorescent fixture荧光灯支架
无尘室日常用品
Anti-static glove 放静电手套 6116930090
Anti-static cloths放静电服(涤纶) 6211339091
Anti-static cap 放静电帽子 65059090
Sticky mat 粘尘垫 39269090
Clean wiper 无尘布 H.S CODE:6307100090
防静电椅子:94018090
Ceiling HEPA Filter Module 高效一体化
Aluminum separator 铝箔 7607200000
滤纸 Minipleat type 4805400000
白色密封条 4016999000
5603949090 初效棉
39081090 尼龙网
Source from: www.cleanroomffu.com
Prepared by: Vanessa Wang
Skype: wangvanlu
2014年5月18日星期日
FFU use Manual
Specification
Fan Filter Unit
1. Characteristic and use of the production
The Fan Filter Unit (FFU) is very universal
purification equipment, normally installing on the every kind of frame, and it
can form a highly clean environment for working. It has good effects on
improving the clean-room’s condition, the quality of the production and the
proportion of the finished product. The Workstation can widely use in every
kinds of industry department and science lab, such as electron, national defense,
exact instrument, pharmacy, agriculture and biology.
2. Parameter specification
Specification
Parameter Model
No.
|
AL-FFU1175
|
Standard
Dimension
|
1175*575*370mm
|
Air Flow
|
1000
|
Average of Air
Speed
|
|
Efficiency of
Filter
|
99.99%
|
Noise
|
≤65dB
|
Rating Power
|
160 W
|
Power Supply
|
220V
|
Weight
|
|
Dimension for
Hepa Filter
|
1170*570*69mm
|
3. The structure’s characteristic and element
1. The structure’s characteristic
As the sketch
map, the Flow Workstation makes up of cabinet, centrifugal fan, HEPA filter and
operational on-off. The cabinet material use cold board plastic coated. The
clean cells use the wind system that can change wind power. Through this
process of changing, the average wind speed in the clean working area will keep
in a rated range (0.3~0.45m /s).
This can prolong the using time of air filter.
2. The element of working
The airs go through the pre
filter, then into the pressure cabin by centrifugal fan, and go through the
hepa filter at last. At this time, the clean air could come out and flow to the
working area. The pressure in the working area is not same, so this can prevent
the dust from outside. In order to enlarge the area of purification, we’d
better use a dispersing component at air exit.
The
Sketch Map of the Workstation
1
Sliding Handle
2
Pre-filter
3
Adjustable Component
4
Fan
5 Hepa Filter
4.
Adjust installation
1.
You’d better put this
production in the highly rate clean environment, at least 100 thousand rate.
2.
The place you install it,
should be away from the dust and the hypocenter.
3.
As the map, the FFU should
be installed from outside purification area, and be rooted by angle iron.
4.
If you change the pre
filter and high filter, you should do it according to this step: 1> the pre filter
just need carry up it, then changes a new one.2> the hepa filter, you need
open the cover board on the back, and then change it.
5. The operation of using
1.
In order to ensure the
purification in clean area, open the power for 15 minutes before using.
2.
If you don’t use for a long
time, please pull out the power pin. And before you stop using, you need clean
it with the cleaner and some other tools that can’t produce fiber. If you use
it again, do this in the same way.
3.
Do not have boil action in
the purification area.
4.
According to your need,
ensure the times of change the air.
5.
According to your need,
adjust the fan’s rate.
6.
Do not put the sundries
outside the pre-filter, in that case, it will reduce the wind and the ability
of purification.
6. The analyzing and removing to troubles
Troubles
|
Reason
|
Solving
|
The average wind
speed is under or up the Wind Rating
|
The fan ‘s
pressure is too low or too high
|
Adjust the switch
of the fan’s speed
|
The wind speed is
slow although the switch has changed into the highest.
|
1.
Too much dust in Pre-filter
2.
The HEPA filter is disabled
|
1.
Clean or change a new
pre-filter
2.
Change a new HEPA filter
|
The fan isn’t running
|
Power line can’t
use
|
Examine the power
line
|
7.
Maintaining of FFU
1.
According to the clean rate in
environment, you need to change the air filter timely. (usually 1~6 months)
2.
When you change the pre-filter
or HEPA filter, please stop the FFU first.
3.
Remarks in changing HEPA
filter:
1)
Please be carful in changing
the HEPA filter, in order to make sure the filter is whole.
2)
When changing a new HEPA
filter, open the cover board first, takes off the old one and then fit on the
new HEPA filter.
8. Transporting and storing
This purification cell could be transported
by normal vehicle, but in this process, make sure it’s water-proof.
This purification cell should be stored in
the house that temperature is between -10℃ ~
+40℃ ;the relative humidity should be
lower than 80% and without acid and alkali corrosive gas.
The storing time limit can exceed 180 days
in the state of having been packed.
9. Examine
1.
When you open the box,
please be careful for fear damage the purification cell.
2.
When you open the box,
please check it whether it is your order production. If you have any question,
please contact me in a week.
3.
Please pay attention to
following circumstances:
1)
Do not operate the power switch
in a short time again and again.
2)
This production can not have
guard against riot ability, so do not operate in the circumstance of flammability
and easy-blast.
3)
Please do not touch the element
in the production. If you really need, please cut off the power first.
4)
Strictly prohibit refit the
machine, or it will result in getting an electric shock or fire.
5)
When you need to examine the
machine, please cut off power.
6)
Do not put heavy thing on the
power line, or else it will be broken to get an electric shock or fire.
7)
When you change a new fuse,
please make sure its capacitance is in the rated lost.
8)
If you do not use for a long
time, please pull out the BNC connector plugs.
9)
If there is some special things
happened, please stops using and connected our company.
10) Please connect the power line with a natural BNC connector jack.
10. Attached Drawing
Equipment warranty card
Product
|
|
Period of
validity
|
|
Model №
|
|
||
Producing
date
|
|
The follow the
table be wrote by the retailer.
Customers name
|
|
Contact №
|
|
Address
|
|
Postcode
|
|
Purchase date
|
|
Retailer
(with stamp)
|
Guangzhou
Anlai Cleantech Co., Ltd.
|
||
Contact name
|
|
Telephone
|
86 138
26021570
|
Anlai Cleantech Co., Ltd.
(Stamp)
编 号
|
ALWV110810
|
检
验 报
告
TEST
REPORT
产品名称: Fan Filter Unit
NAME OF SAMPLE
型号规格:1175*575*290mm
TRADE MARK & TYPE
Product
name
|
Fan
filter unit
|
Measurement
|
1175*575*290mm
|
||||||
Inspection
sort
|
Factory inspection
|
||||||||
Inspection
items
|
(1)HEPA filter
|
||||||||
(2)Technology terms
|
|||||||||
Test Results
|
|||||||||
N0.
|
Test Items
|
Technology
Requirement
|
Test
Result
|
Result
|
|||||
1
|
Appearance
|
No
scar, no uneven and uniformity of spray-paint
|
pass
|
|
|||||
2
|
Size
|
Measurement
base on draft
|
pass
|
|
|||||
3
|
Efficiency
|
Filter
efficiency
99.99%@0.3um
|
pass
|
|
|||||
4
|
Air
flow
|
1000~
|
pass
|
|
|||||
6
|
Noise
(test away from
|
<65db
|
pass
|
|
|||||
7
|
Air
velocity of nozzles (m/s)
|
0.3
|
pass
|
|
|||||
Result
|
|
||||||||
Inspector
|
|
Date
|
|
||||||
Guangzhou RKS Airclean Equipment
Manufacturing Co., Ltd.
订阅:
博文 (Atom)