ISO14644-1 and FS209E Cleanroom Standards
Anlaitech is the leading expert in the
design and fabrication of critical-environment applications. We offer a
complete range of clean room equipment, furnishing and supplies for cleanrooms
and laboratories. Following are the rigorous standards to which Anlaitech
adheres.
Before global cleanroom classifications and
standards were adopted by the International Standards Organization (ISO), the
U.S. General Service Administration’s standards (known as FS209E) were applied
virtually worldwide. However, as the need for international standards grew, the
ISO established a technical committee and several working groups to delineate
its own set of standards.
FS209E contains six classes, while the ISO
14644-1 classification system adds two cleaner standards and one dirtier
standard (see chart below). The "cleanest" cleanroom in FS209E is
referred to as Class 1; the "dirtiest" cleanroom is a class 100,000.
ISO cleanroom classifications are rated according to how much particulate of
specific sizes exist per cubic meter (see second chart). The
"cleanest" cleanroom is a class 1 and the "dirtiest" a
class 9. ISO class 3 is approximately equal to FS209E class 1, while ISO class
8 approximately equals FS209E class 100,000.
By law, Federal Standard 209E can be
superseded by new international standards. It is expected that 209E will be
used in some industries over the next five years, but that eventually it will
be replaced internationally by ISO 14644-1.
Airborne Particulate Cleanliness Class
Comparison
ISO 14644-1
|
FEDERAL STANDARD 209E
|
|
ISO Class
|
English
|
Metric
|
ISO 1
|
||
ISO 2
|
||
ISO 3
|
1
|
M1.5
|
ISO 4
|
10
|
M2.5
|
ISO 5
|
100
|
M3.5
|
ISO 6
|
1,000
|
M4.5
|
ISO 7
|
10,000
|
M5.5
|
ISO 8
|
100,000
|
M6.5
|
ISO 9
|
Airborne Particulate Cleanliness Classes
(by cubic meter):
CLASS
|
Number of Particles per Cubic Meter by
Micrometer Size
|
|||||
0.1 micron
|
0.2 micron
|
0.3 micron
|
0.5 micron
|
1 micron
|
5 microns
|
|
ISO1
|
10
|
2
|
||||
ISO2
|
100
|
24
|
10
|
4
|
||
ISO3
|
1,000
|
237
|
102
|
35
|
8
|
|
ISO4
|
10,000
|
2,370
|
1,020
|
352
|
83
|
|
ISO5
|
100,000
|
23,700
|
10,200
|
3,520
|
832
|
29
|
ISO6
|
1,000,000
|
237,000
|
102,000
|
35,200
|
8,320
|
293
|
ISO7
|
352,000
|
83,200
|
2,930
|
|||
ISO8
|
3,520,000
|
832,000
|
29,300
|
|||
ISO9
|
35,200,000
|
8,320,000
|
293,000
|
In cleanrooms, particulate concentration
changes over time — from the construction and installation of equipment to its
operational status. ISO delineates three cleanroom classification standards:
as-built, at-rest and operational. As instruments and equipment are introduced
and particulates rise, an "as-built" cleanroom becomes an
"at-rest" cleanroom. When people are added to the matrix, particulate
levels rise still further in the "operational" cleanroom.
ISO 14644-2 describes the type and
frequency of testing required to conform to certain standards. The following
tables indicate mandatory and optional tests.
Required Testing (ISO 14644-2)
Schedule of Tests to Demonstrate
Continuing Compliance
|
|||
Test Parameter
|
Class
|
Maximum Time Interval
|
Test Procedure
|
Particle Count Test
|
<= ISO 5
|
6 Months
|
ISO 14644-1 Annex A
|
> ISO 5
|
12 Months
|
||
Air Pressure Difference
|
All Classes
|
12 Months
|
ISO 14644-1 Annex B5
|
Airflow
|
All Classes
|
12 Months
|
ISO 14644-1 Annex B4
|
Optional Testing (ISO 14644-2)
Schedule of Additional Optional Tests
|
|||
Test Parameter
|
Class
|
Maximum Time Interval
|
Test Procedure
|
Installed Filter Leakage
|
All Classes
|
24 Months
|
ISO 14644-1 Annex B6
|
Containment Leakage
|
All Classes
|
24 Months
|
ISO 14644-1 Annex B4
|
Recovery
|
All Classes
|
24 Months
|
ISO 14644-1 Annex B13
|
Airflow Visualization
|
All Classes
|
24 Months
|
ISO 14644-1 Annex B7
|
Today, in addition to ISO 14644-1 and ISO
14644-2, eight other cleanroom standards documents are being prepared. Many are
in the final voting stage and can be legally used in the trade (see chart).
ISO Document
|
Title
|
ISO 14644-1
|
Classification of Air Cleanliness
|
ISO 14644-2
|
Cleanroom Testing for Compliance
|
ISO 14644-3
|
Methods for Evaluating and Measuring
Cleanrooms and Associated Controlled Environments
|
ISO 14644-4
|
Cleanroom Design and Construction
|
ISO 14644-5
|
Cleanroom Operations
|
ISO 14644-6
|
Terms, Definitions and Units
|
ISO 14644-7
|
Enhanced Clean Devices
|
ISO 14644-8
|
Molecular Contamination
|
ISO 14698-1
|
Biocontamination: Control General
Principles
|
ISO 14698-2
|
Biocontamination: Evaluation and
Interpretation of Data
|
ISO 14698-3
|
Biocontamination: Methodology for Measuring
Efficiency of Cleaning Inert Surfaces
|
The USA source for ISO documents is:
Institute of Environmental Sciences &
Technology (IEST)
The source for FS209E documents at
the General Services Administration is:
Naval Publications and Forms Center
Naval Publications and Forms Center
ISO and Federal Air Change Rates for
Cleanrooms
A critical factor in cleanroom design is
controlling air-change per hour (ACH), also known as the air-change rate, or
ACR. This refers to the number of times each hour that filtered outside air
replaces the existing volume in a building or chamber. In a normal home, an
air-conditioner changes room air 0.5 to 2 times per hour. In a cleanroom,
depending on classification and usage, air change occurs anywhere from 10 to
more than 600 times an hour.
ACR is a prime variable in determining ISO
and Federal cleanliness standards. To meet optimal standards, ACR must be
painstakingly measured and controlled. And there is some controversy. In an
appendix to its ISO 14644-1 cleanliness standard, the International Standards
Organization addressed applications for microelectronic facilities only. (ISO
classes 6 to 8; Federal Standards 1,000, 10,000 and 100,000.) The appendix
contained no ACR standards for pharmaceutical, healthcare or biotech
applications, which may require higher ACR regulations.
According to current research, case studies
and experiments, using an ACR range (rather than one set standard) is a better
guideline for cleanliness classification. This is true because the optimal ACR
varies from cleanroom to cleanroom, depending on factors such as internal
equipment, staffing and operational purpose. Everything depends on the level of
outside contaminants trying to enter the facility versus the level of
contaminants being generated on the inside.
The breadth of these ranges reflects how
dramatically people and processes affect cleanliness. Low-end figures within
each contamination class generally indicate air velocity and air change
requirements for an as-built or at-rest facility—where no people are present
and no contaminating processes under way. When there are people and processes
producing contaminants, more air changes are required to maintain optimal
cleanliness standards. For instance, some manufacturers insist on as many as
720 air changes per hour to meet Class 10 standards.
Determining the appropriate number of air
changes for a particular application requires careful evaluation of factors
such as the number of personnel, effectiveness of garbing protocol, frequency
of access, and cleanliness of process equipment.
Rajan Jaisinghani, in his paper
"Energy Efficient Low Operating Cost Cleanroom Airflow Design,"
presented at ESTECH 2003, recommended the following ranges based on FS209E
classifications:
FS Cleanroom Class
|
ISO Equivalent Class
|
Air Change Rate
|
1
|
ISO 3
|
360-540
|
10
|
ISO 4
|
300-540
|
100
|
ISO 5
|
240-480
|
1,000
|
ISO 6
|
150-240
|
10,000
|
ISO 7
|
60-90
|
100,000
|
ISO 8
|
5-48
|
Jaisinghani’s recommendations concur with
other recent studies of ACR, which criticize some existing air rate standards
(developed in the 1990s) as being unscientific because they are based on fans
and filters inferior to today’s models. So when these older standards are
applied, the resulting ACR is often too high. In fact, some studies have found
that reducing the ACR (and its attendant air turbulence) can result in a
cleaner atmosphere.
This was demonstrated in a study conducted
by Pacific Gas and Electric (San Francisco) and the Lawrence Berkeley National
Laboratory (Berkeley). The study measured air change rates in several ISO
Class-5 cleanrooms and came to the conclusion that there is "no consistent
design strategy for air change rate, even for cleanrooms of the same
cleanliness classification."
ACR rates have critical design
implications, especially when considering desired cleanliness, fan size and
lower energy costs. The PG&E/Berkeley study caused many designers to reduce
fan sizes. In short, a lower ACR often resulted in cleaner air.
The study revealed three abiding
principles:
- Lower air change rates result in smaller fans, which reduce both initial investment and construction cost.
- Fan power is proportional to the cube of air change rates or airflow. A 30-percent reduction in air change rate results in a power reduction of approximately 66 percent.
- By minimizing turbulence, lower airflow may improve cleanliness.
The study focused on Class-5 cleanrooms,
concluding that an ACR range of from 250 to 700 air changes per hour is
standard, but that "actual operating ACRs ranged from 90 to 625." It
added that all of these optimized cleanrooms were certified and performing at
ISO Class-5 conditions with these lower ACRs. Finally, the study concluded that
rarely does a Class-5 facility require an ACR of more than 300.
The study also found that the "[b]est
practice for ACRs is to design new facilities at the lower end of the
recommended ACR range," with variable speed drives (VSDs) built in so that
air flow adjustments can be made under actual operating conditions.
In his report "An examination of ACRs:
An opportunity to reduce energy and construction costs," Peter Rumsey, PE,
CEM, essentially concurred with the PG&E-commissioned study by Berkeley.
Rumsey issued a caveat, then brushed it aside by citing research subsequent to
Berkeley’s: "Air cleanliness is a critical component of any cleanroom, far
outweighing energy saving priorities. Designers and operators need evidence
from others who have tried similar strategies in order to address the perceived
risks of lowering air change rates."
Rumsey then went on to cite studies done by
International Sematech (Austin, Texas); the Massachusetts Institute of
Technology (Cambridge, Mass.); Intel (Santa Clara, Calif.); and Sandia National
Laboratories (Albuquerque, N.M.), which echoed the Berkeley study.
In summary, current research and thinking
on air change rates indicate that some existing standards are too high and can
be lowered while still meeting all ACR criteria.
Federal and ISO Ceiling Fan Coverage
Specifications
Achieving the optimal air change rate
requires proper ceiling fan coverage. The cleanest modular cleanroom
incorporates filter/fan units (FFUs) in every 2’ x 4’ (610 mm x 1219 mm)
ceiling bay. This near-100% coverage provides a laminar flow of filtered air to
quickly remove contaminants from the room, thus meeting FS209E standards for
Class 10 and ISO Class 1 standards.
Such coverage, especially in a large
cleanroom, can lead to higher energy consumption, thus increasing costs for
both initial construction and ongoing operation. In most cases, a smaller
percentage of ceiling coverage produces adequate cleanliness.
This table illustrates the percentage of
ceiling coverage recommended for each cleanliness class, again as a range:
Class
|
Ceiling Coverage (Percentage)
|
ISO 8 (Class 100,000)
|
5 – 15%
|
ISO 7 (Class 10,000)
|
15 – 20%
|
ISO 6 (Class 1,000)
|
25 – 40%
|
ISO 5 (Class 100)
|
35 – 70 %
|
ISO 4 (Class 10)
|
50 – 90%
|
ISO 3 (Class 1)
|
60 – 100%
|
ISO 1-2
|
80 – 100%
|
Federal and ISO Airflow Velocity
Standards
In addition to ACR and ceiling coverage,
the third factor integral to maintaining cleanliness is fan-generated air speed.
Again, higher airflow velocity results in a "cleaner" cleanroom. The
term "ventilation efficiency" refers to the speed of filtered air
passing through the cleanroom in addition to the number of air changes per hour
(ACH or ACR).
An earlier chart showed a range of
recommended air change rates (ACRs) for different classes of cleanrooms. Ranges
are given because as-built and at-rest facilities require a smaller ACR than an
operational cleanroom, where both people and equipment are actively engaged. Non-operational
cleanrooms are found in the lower range; operational cleanrooms higher.
Combining all three factors—ACR, ceiling
coverage and airflow velocity—results in the following table:
Class ISO 146144-1 (Federal Standard
209E)
|
Average Airflow Velocity
m/s (ft/min) |
Air Changes Per Hour
|
Ceiling Coverage
|
ISO 8 (Class 100,000)
|
0.005 – 0.041 (1 – 8)
|
5 – 48
|
5 – 15%
|
ISO 7 (Class 10,000)
|
0.051 – 0.076 (10 -15)
|
60 – 90
|
15 – 20%
|
ISO 6 (Class 1,000)
|
0.127 – 0.203 (25 – 40)
|
150 – 240
|
25 – 40%
|
ISO 5 (Class 100)
|
0.203 – 0.406 (40 – 80)
|
240 – 480
|
35 – 70%
|
ISO 4 (Class 10)
|
0.254 – 0.457 (50 – 90)
|
300 – 540
|
50 – 90%
|
ISO 3 (Class 1)
|
0.305 – 0.457 (60 – 90)
|
360 – 540
|
60 – 100%
|
ISO 1 – 2
|
0.305 – 0.508 (60 – 100)
|
360 – 600
|
80 – 100%
|
Before deciding on the appropriate velocity
and air changes for your application, Terra Universal recommends careful
evaluation of factors such as number of personnel, effectiveness of garbing
protocol, access frequency and cleanliness of process equipment. Once the
required air change figure is established, the number of required FFUs can be
determined using this formula: No. of FFUs = (Air Changes/Hour ÷60) x
(Cubic ft. in room÷ 650*)
*CFM output of a loaded FFU
*CFM output of a loaded FFU
Meeting Class 100 standards using the
low-end air change recommendation (240/hour) inside a 12’ x 12’ x 7’ (3302 mm x
3302 mm x 2134 mm) cleanroom, with 1008 cu. ft. of volume, requires 6 FFUs. To
meet the same standard using the high-end air change recommendation (480/hour)
requires 12 FFUs.
Positive Pressure
Cleanrooms are designed to maintain
positive pressure, preventing "unclean" (contaminated) air from
flowing inside and less-clean air from flowing into clean areas. The idea is to
ensure that filtered air always flows from cleanest to less-clean spaces. In a
multi-chambered cleanroom, for instance, the cleanest room is kept at the
highest pressure. Pressure levels are set so that the cleanest air flows into
spaces with less-clean air. Thus, multiple pressure levels may need to be
maintained.
A differential air pressure of 0.03 to 0.05
inches water gauge is recommended between spaces. In order to ensure that
pressure differentials remain constant when doors are opened, or other events
occur, control systems must be in place.
Laminar and Turbulent Air Flow
ISO 5 (Class 100) and cleaner facilities
rely on unidirectional, or laminar, airflow. Laminar airflow means that
filtered air is uniformly supplied in one direction (at a fixed velocity) in
parallel streams, usually vertically. Air is generally recirculated from the
base of the walls back up to the filtering system.
ISO 6 (Class 1,000) and above cleanrooms
generally utilize a non-unidirectional, or turbulent, airflow. This means the
air is not regulated for direction and speed. The advantage of laminar over
turbulent airflow is that it provides a uniform environment and prevents air
pockets where contaminants might congregate.
没有评论:
发表评论